Global Global Algérie Français Algeria English Angola Português Angola English Argentina Español Argentina English Australia English Austria Deutsch Austria English Azerbaijan English Azerbaijan Русский Bahrain English Bangladesh English Belgium English Belgium Français Belgium Nederlands Brazil Português Brazil English Bulgaria български Bulgaria English Cameroon English Cameroon Français Canada English Canada Français Chile Español Chile English China 中文 China 日本語 China English Colombia Español Colombia English Croatia English Czech Republic Čeština Czech Republic English Denmark English Djibouti English Ecuador Español Ecuador English Egypt English Estonia English Ethiopia English Finland Suomi Finland English France Français France English Georgia English Georgia Русский Germany Deutsch Germany English Ghana English Greece Ελληνικά Greece English Guatemala Español Guatemala English Hong Kong, China English Hong Kong, China 中文 Hungary Magyar Hungary English India English Indonesia English Iraq English Ireland English Italy Italiano Italy English Ivory Coast Français Ivory Coast English Japan 日本語 Japan English Jordan English Kazakhstan Русский Kazakhstan English Kenya English Kuwait English Kyrgyzstan Русский Kyrgyzstan English Latvia English Lithuania English Malaysia English Mauritius English Mauritius français (Maurice) Mexico Español Mexico English Moldova Română Moldova English Mongolia English Morocco English Morocco Français Mozambique Português Mozambique English Netherlands Nederlands Netherlands English New Zealand English Nigeria English Norway English Oman English Pakistan English Paraguay Español Paraguay English Peru Español Peru English Philippines English Poland Polski Poland English Portugal Português Portugal English Qatar English Republic of Korea 한국어 Republic of Korea English Romania Română Romania English Saudi Arabia English Serbia Српски Serbia English Singapore English Slovakia English Slovenia English South Africa English Spain English Spain Español Sri Lanka English Sweden English Switzerland Deutsch Switzerland Français Switzerland Italiano Switzerland English Tanzania English Thailand ไทย Thailand English Togo English Togo Français Tunisia English Tunisia Français Türkiye Türkçe Türkiye English Turkmenistan Русский Turkmenistan English Ukraine Українська Ukraine English United Arab Emirates English United Kingdom English Uruguay Español Uruguay English USA English Uzbekistan English Uzbekistan Русский Vietnam Tiếng Việt Vietnam English

Entrusted testing of fire-fighting foam liquids provides manufacturers, distributors, and end users with independent, standards-based verification of foam concentrate quality and firefighting performance. Accredited third-party laboratories evaluate physical properties, foam expansion and drainage characteristics, and full-scale fire suppression capability in accordance with standards such as GB 15308, ISO 7203, EN 1568, and UL 162. This article explains the sample types, testing items, test methods, and typical applications of a commissioned foam liquid inspection program.

Technical Overview

Fire-fighting foam liquid, more precisely referred to as foam concentrate, is an aqueous solution of surfactants, foam stabilizers, solvents, and functional additives that, when proportioned with water and aerated through suitable equipment, produces an expanding foam blanket used to suppress Class B flammable liquid fires and, in some formulations, Class A fuel fires. Because the extinguishing effectiveness of foam depends directly on the chemical integrity of the concentrate, systematic laboratory verification is essential.

Entrusted testing, also known as commissioned inspection or client-commissioned testing, is a formal arrangement in which a client engages an accredited third-party laboratory to test a submitted sample against a specified standard and issue an objective test report. Unlike internal factory quality control, an entrusted test report carries independent credibility and is widely accepted for product registration, procurement acceptance, bidding documentation, and regulatory compliance.

The governing technical frameworks for foam concentrate testing include GB 15308 (foam extinguishing agents), the ISO 7203 series (foam concentrates for media and high expansion applications on non-polar and polar solvents), the EN 1568 series (low, medium, and high expansion foam concentrates), and UL 162 (foam equipment and liquid concentrates). Additional sector requirements, such as IMO and ICAO performance criteria for marine and airport applications, may also be invoked depending on the end use of the product.

Testing Samples

Aqueous Film-Forming Foam (AFFF) Concentrates

AFFF concentrates at 1%, 3%, and 6% nominal proportioning rates are among the most frequently submitted sample types. Testing focuses on film formation and sealability over hydrocarbon fuel surfaces, expansion ratio, drainage time, and extinguishing performance on standardized fuel pans. Both fresh stock and aged or in-service product may be submitted for comparison against original specifications.

Alcohol-Resistant Foam Concentrates (AR-AFFF, AR-FFFP, AR-FP)

Alcohol-resistant formulations contain polymers that form a protective membrane on polar solvent fuels such as ethanol, acetone, and isopropanol. Entrusted testing for these products includes both hydrocarbon fire tests and polar solvent fire tests, together with verification of the polymer module formation and foam stability in the presence of water-miscible fuels.

Protein and Fluoroprotein Foam Concentrates (P, FP, FFFP)

Protein-based concentrates derived from hydrolyzed protein are tested for sediment content, viscosity behavior, and resistance to burnback. Fluoroprotein and film-forming fluoroprotein types additionally require film formation assessment. These products are commonly submitted by petrochemical storage terminal operators and fixed foam system owners.

Synthetic and High Expansion Foam Concentrates (S, M, Class A)

Synthetic detergent-based concentrates, medium and high expansion concentrates, and Class A wetting agents for structural and wildfire applications are submitted for expansion ratio testing across the appropriate range, drainage measurement, and, where applicable, fuel-specific fire performance verification.

Sample Submission Requirements

Typical requirements for an entrusted test include submission of unopened, factory-sealed containers representing the production batch; a minimum volume usually in the range of 20 to 50 liters depending on the test scope; batch number, production date, and proportioning rate documentation; a safety data sheet; and a completed commissioning agreement identifying the test standard and requested items. Samples should be transported without exposure to freezing or excessive heat to avoid altering their properties before analysis.

Testing Items

A comprehensive entrusted test program for foam liquid concentrates generally covers three tiers of performance evaluation:

  • Physical and chemical properties: density, viscosity (as-supplied and at low shear rates), pH value, freezing point or fluidity at low temperature, sediment content, water content, corrosion behavior toward carbon steel, stainless steel, and brass coupons, and pourability after thermal cycling.
  • Foam generation characteristics: expansion ratio measured in the low (below 20:1), medium (20:1 to 200:1), or high (above 200:1) range as appropriate; 25% drainage time; foam stability at elevated temperature; and, for film-forming products, film formation and sealability time over reference fuels.
  • Fire suppression performance: 90% flame control time, extinguishing time, 25% burnback resistance time, and total extinguishing performance on standardized Class B fuel fires, with separate assessment against polar solvents for alcohol-resistant grades.
  • Durability and environmental items: low temperature stability and recovery, aging and storage stability, compatibility with fresh or sea water, and, where contractually requested, assessment of fluorine-free or environmentally optimized formulations.

Testing Methods

Physical and chemical tests are conducted using calibrated laboratory instrumentation: density meters or hydrometers, rotational viscometers, precision pH electrodes, cryostats for freezing point and low temperature fluidity determination, and gravimetric procedures for sediment measurement following standard-defined centrifugation or settling protocols.

Foam performance testing employs standardized foam generation apparatus, typically a reference branch pipe or discharge nozzle operated at defined pressure, flow rate, and water temperature. Expansion ratio is determined by measuring the mass of foam collected in a calibrated vessel, while 25% drainage time is measured with a drainage screen assembly that captures the time for one quarter of the foam solution mass to drain from the generated foam.

Fire performance tests are performed on outdoor or indoor fire test platforms using standardized square fuel pans, commonly 1.5 square meters or 4.52 square meters in area depending on the standard invoked. A defined depth of reference fuel, typically heptane or standard gasoline, is ignited and pre-burned for a prescribed period before foam application at the specified application rate. Instrumented timing records flame control, extinguishment, and subsequent burnback response after ignition of a central burnback pot. All fire tests are conducted under documented wind, temperature, and fuel conditions to ensure reproducibility and comparability with the acceptance criteria of GB 15308, ISO 7203, EN 1568, or UL 162 as selected by the client.

Applications

Entrusted foam liquid testing serves a wide range of commercial, regulatory, and engineering purposes:

  • New product development and type certification: verification that a newly formulated concentrate meets all acceptance criteria prior to market introduction or inclusion in product certification schemes.
  • Batch release and factory acceptance: independent confirmation that production lots conform to declared specifications before shipment to customers.
  • Procurement and tender verification: evaluation of competing products during purchasing decisions by fire brigades, airports, refineries, chemical plants, tank farm operators, and marine operators.
  • In-service stock verification: periodic testing of stored concentrates to detect degradation, stratification, sediment growth, or loss of fire performance beyond manufacturer shelf-life claims.
  • System commissioning support: confirmation that the concentrate delivered to a fixed foam extinguishing system matches the performance basis used in the engineering design.
  • Incident investigation and claims: retrospective analysis of foam performance following fire events, system activations, or disputed deliveries.

FAQ

How much sample is required for an entrusted test?

For a full performance test including fire testing, laboratories typically request 25 to 50 liters of concentrate. Smaller volumes may suffice if only physical and chemical items are commissioned.

Which standard should be selected for testing?

The choice depends on the market and application: GB 15308 is generally applied for products sold and used domestically in China, while ISO 7203, EN 1568, and UL 162 are selected for international trade or project-specific specifications. Sector rules such as IMO or ICAO criteria may be added for marine and aviation firefighting products.

How long does the testing process take?

Physical and chemical analysis typically requires one to two weeks. Full programs including fire performance and burnback testing generally require three to six weeks, depending on laboratory scheduling and weather conditions for outdoor fire tests.

Is an entrusted test report the same as a product certificate?

No. An entrusted test report provides objective test results for a specific sample. Product certification additionally involves factory audits, ongoing surveillance, and scheme-specific rules administered by certification bodies. Entrusted test reports are, however, frequently used as the technical basis within such certification processes.

Do stored foam concentrates require periodic retesting?

Yes. Industry practice recommends periodic verification of in-service stocks, commonly at intervals of one to three years or at the end of the manufacturer-declared service life, because concentrates can stratify, form sediment, or lose fire performance during long-term storage.

Can diluted or premixed foam solutions be tested?

Testing is normally performed on the original concentrate, since fire performance criteria are defined for foam generated from the as-supplied product. However, commissioned analysis of premixed solutions can be performed for stability investigations or incident reconstruction when clearly defined as a custom test scope.